PSI-99
SAFFIRE-II
Spacecraft Fire Experiment-II
Where its tests sit
This investigation's own test rows on the chart of the evidence; the red frame is the Moon base / rover region. Switch habitats on the dashboard.
Oxygen, % by volume →
Key facts
- Oxygen tested
- 21.5–22.1 % O₂
- Pressure tested
- Not reported
- Airflow tested
- 20 cm/s
- Fuel phase
- Solid fuel
- Gravity
- Microgravity
- Platform
- Cygnus Spacecraft
- Hardware
- Cygnus Pressurized Cargo Module, SAFFIRE
- Hardware family
- Large-scale spacecraft firesSaffire enclosure on the Cygnus cargo vehicle, after it left the ISS
- Sample / burner size
- Samle Thickness: 0.27 mm, 0.61 mm, 1.03 mm, 037 mm +3 more
- Sample Length: 29 cm, 5 and 24 cm
- Sample Width (cm): 5 cm
Objective
The SAFFIRE-II investigation aims to determine how rapidly a large-scale fire grows in low gravity and to evaluate low-g flammability limits relative to NASA's terrestrial screening tests.
Key findings
Cotton-Fiberglass (SIBAL) burned for 145 seconds in low gravity with a 29 cm burn length and 2.1 mm/s spread rate, whereas silicone samples had insignificant burn times and near-zero microgravity burn lengths.
Earth applications
Fire studies in small, sealed environments like Cygnus benefit terrestrial fire safety and prevention efforts in confined spaces such as mines, airplanes, or submarines.
Fuels and samples
- Silicone
- Cotton-Fiberglass (SIBAL)
- PMMA & Nomex
- PMMA
Sensors and measurements
- cameras
- thermocouples
- radiometers
- solid state sensors
- anemometer
How the tests differed
What changed from one test to the next, and what stayed fixed, read straight from NASA's test table. Dates, times and test numbers are left out.
Varied between tests (12)
- Material · 4 values, e.g. Silicone; Cotton-Fiberglass (SIBAL); PMMA & Nomex (2 blank)
- Samle Thickness · 7 values, e.g. 0.27 mm; 0.61 mm; 1.03 mm
- Sample Length · 2 values, e.g. 29 cm; 5 and 24 cm
- Percent O2 (Note 1) · 4 values, e.g. ~ 21.5; ~ 22.1; 22.1 to 22.0
- Ignition Power (W) · 2 values, e.g. 80 W; 97 W
- Ignition Time (s) · 2 values, e.g. 9.2 s; 30 s
- Burn Time (s) · 6 values, e.g. Insignificant; 145 s; 115 s
- Flow Direction · 2 values, e.g. Concurrent; Opposed
- ?-g Burn Length · 5 values, e.g. ~ 0; 29 cm; 5 cm & 0 (note 2)
- ?-g Spread Length · 5 values, e.g. n/a; 2.1 mm/s; 2.6 mm/s
- 1-g Burn Length · 4 values, e.g. Complete; 7.6 cm; ~ 0
- 1-g Spread Rate · 5 values, e.g. Acceleratory; 1.2 mm/s; n/a
Same in every test (2)
- Sample Width (cm) · 5 cm
- Air Flow (cm/s) · 20 cm/s
Score in each scenario
Focus: all pillars, each scenario's default ventilation. Full reasons are in the dashboard table.
| Scenario | Rank | Score | A · B · C · D · E |
|---|---|---|---|
| ISS cabin | #2 of 24 | 93.4 | |
| Moon base / pressurized rover | #1 of 24 | 84.8 | |
| Spacesuit | #2 of 24 | 49 |
Test table (9 rows)
Test rows from NASA's experimental-table CSV, every cell exactly as published (6 non-test rows set aside, see Data cleaning). Download as CSV · Compare with all tests in the Data Explorer
Experimental table
| Sample Number | Material | Samle Thickness | Sample Length | Sample Width (cm) | Air Flow (cm/s) | Percent O2 (Note 1) | Ignition Power (W) | Ignition Time (s) | Burn Time (s) | Flow Direction | ?-g Burn Length | ?-g Spread Length | 1-g Burn Length | 1-g Spread Rate | Camera 1 | Camera 2 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2-1 | Silicone | 0.27 mm | 29 cm | 5 cm | 20 cm/s | ~ 21.5 | 80 W | 9.2 s | Insignificant | Concurrent | ~ 0 | n/a | Complete | Acceleratory | S1C1 | S1C2 |
| 2-2 | Silicone | 0.61 mm | 29 cm | 5 cm | 20 cm/s | ~ 22.1 | 80 W | 9.2 s | Insignificant | Concurrent | ~ 0 | n/a | 7.6 cm | 1.2 mm/s | n/a | S2C2 |
| 2-3 | Silicone | 1.03 mm | 29 cm | 5 cm | 20 cm/s | ~ 22.1 | 80 W | 9.2 s | Insignificant | Concurrent | ~ 0 | n/a | ~ 0 | n/a | S3C2 | |
| 2-4 | Silicone | 037 mm | 29 cm | 5 cm | 20 cm/s | ~ 22.1 | 80 W | 9.2 s | Insignificant | Opposed | ~ 0 | n/a | Complete | 0.6 mm/s | S4C1 | S4C1 |
| 2-5 | Cotton-Fiberglass (SIBAL) | 037 mm | 29 cm | 5 cm | 20 cm/s | ~ 22.1 | 80 W | 9.2 s | 145 s | Concurrent | 29 cm | 2.1 mm/s | Complete | Acceleratory | S5C1 | S5C2 |
| 2-6 | 037 mm | 29 cm | 5 cm | 20 cm/s | ~ 22.1 | 80 W | 9.2 s | 115 s | Concurrent | 29 cm | 2.6 mm/s | Complete | Acceleratory | S6C1 | S56C2 | |
| 2-7 | PMMA & Nomex | 0.85 and 0.37 mm | 5 and 24 cm | 5 cm | 20 cm/s | ~ 22.1 | 80 W | 9.2 s | 140 s | Concurrent | 5 cm & 0 (note 2) | n/a (Nomex) | ~ 0 (Nomex) | n/a (Nomex) | S7C1 | n/a |
| 2-8 | PMMA | See Fig. 5 | 29 cm | 5 cm | 20 cm/s | 22.1 to 22.0 | 97 W | 30 s | 600 s | Concurrent | ~ 10 cm (note 3) | Note 4 | Complete | Acceleratory | S8C1 | n/a |
| 2-9 | 1 cm | 29 cm | 5 cm | 20 cm/s | 22.0 to 21.9 | 97 W | 30 s | 900 s | Concurrent | ~ 10 cm (note 4) | Note 4 | Complete | Acceleratory | S9C1 | n/a |
Data cleaning
What the row-by-row check of NASA's CSV found. Rows that are not tests are set aside (not deleted from the source); problems in kept rows are flagged, never silently fixed.
PSI-99_Experimental table_SAFFIRE-2.csv · 15 CSV rows → 9 test rows
Set aside (6)
- row 10 flow-visualization reference with no test dataF1C1/F1C2 | Pre-test flow visulation data for sample 2-1
- row 11 flow-visualization reference with no test dataF2C1/F2C2 | Pre-test flow visulation data for sample 2-2
- row 12 footnote line, not a test
- row 13 footnote line, not a test
- row 14 footnote line, not a test
- row 15 footnote line, not a test
Flagged in kept rows (6)
- row 4 Samle Thickness '037 mm' looks like a typo for 0.37 mm (source value kept, not converted)
- row 5 Samle Thickness '037 mm' looks like a typo for 0.37 mm (source value kept, not converted)
- row 6 Samle Thickness '037 mm' looks like a typo for 0.37 mm (source value kept, not converted); Material is blank in the source
- row 7 Samle Thickness '0.85 and 0.37 mm' is a two-layer sample, not one thickness
- row 8 Samle Thickness refers to a figure that is not in the PSI table
- row 9 Material is blank in the source
NASA's notes in this table
- Note 1 Derived from measured CO2 production and referenced to initial O2 concentration reported by ISS.
- Note 2 The PMMA portion was completely consumed but the Nomex was not ignited.
- Note 3 This is the length of fuel with significant visible damage.
- Note 4 The flames remain anchored at the base of the sample which has a very slow regression rate (0.01 to 0.04 mm/s)
Where this came from(source of every field)
| Field | Value | Source |
|---|---|---|
| psi_id | PSI-99 | json:accession |
| acronym | SAFFIRE-II | json:investigationAcronym |
| title | Spacecraft Fire Experiment-II | json:title |
| doi | 10.60555/2chp-m469 | json:doi |
| platform | Cygnus Spacecraft | json:flightProgram |
| hardware | Cygnus Pressurized Cargo Module, SAFFIRE | json:experimentHardware |
| fuel_phase | solid | rule:fuel_phase_seed |
| fuels | Silicone; Cotton-Fiberglass (SIBAL); PMMA & Nomex; PMMA | llmMaterial: Silicone Material: Cotton-Fiberglass (SIBAL) Material: PMMA & Nomex Material: PMMA |
| o2_percent_range | 21.5; 22.1 |
|
| pressure_psi_range | null (not reported) | csv:none |
| airflow_cm_s_range | 20; 20 |
|
| gravity | microgravity | rule:gravity_seed |
| pillars | prevention | rule:pillar_seed |
| measurements | cameras; thermocouples; radiometers; solid state sensors; anemometer | llmOnce the sample was ignited flame images were captured using two cameras. In addition, thermocouples provided flow, flame, and plume temperatures, two radiometers recorded flame radiation, solid state sensors were used to measure pressure, CO2 and O2 mole faction, and two anemometer tracked flow velocity. In addition, thermocouples provided flow, flame, and plume temperatures, two radiometers recorded flame radiation, solid state sensors were used to measure pressure, CO2 and O2 mole faction, and two anemometer tracked flow velocity. In addition, thermocouples provided flow, flame, and plume temperatures, two radiometers recorded flame radiation, solid state sensors were used to measure pressure, CO2 and O2 mole faction, and two anemometer tracked flow velocity. In addition, thermocouples provided flow, flame, and plume temperatures, two radiometers recorded flame radiation, solid state sensors were used to measure pressure, CO2 and O2 mole faction, and two anemometer tracked flow velocity. |
| objective_summary | The SAFFIRE-II investigation aims to determine how rapidly a large-scale fire grows in low gravity and to evaluate low-g flammability limits relative to NASA's terrestrial screening tests. | llmThe objectives of SAFFIRE-II are to determine how rapidly a large scale fire grows in low-gravity and to investigate the low-g flammability limits compared to those obtained in NASA’s normal gravity material flammability screening test. |
| key_findings | Cotton-Fiberglass (SIBAL) burned for 145 seconds in low gravity with a 29 cm burn length and 2.1 mm/s spread rate, whereas silicone samples had insignificant burn times and near-zero microgravity burn lengths. | llm2-5, Cotton-Fiberglass (SIBAL), 037 mm, 29 cm, 5 cm, 20 cm/s, ~ 22.1, 80 W, 9.2 s, 145 s, Concurrent, 29 cm, 2.1 mm/s, Complete, Acceleratory, S5C1, S5C2 |
| earth_applications | Fire studies in small, sealed environments like Cygnus benefit terrestrial fire safety and prevention efforts in confined spaces such as mines, airplanes, or submarines. | llmStudying fire in small, sealed environments such as the Cygnus cargo supply vehicle benefits fire safety and prevention efforts on Earth, including inside mines, airplanes, or submarines. |
| tests | 9 rows |
|
| source_urls | https://psi.nasa.gov/physci/repo/data/investigations/PSI-99 | rule:psi_page |
| extraction_confidence | llm_unchecked | extract/checked_ids.txt |